PRODUCT NAME:
MODEL NO.:
AMC-40WS AMC-50WS AMC-60WS AMC-70WS AMC-80WS AMC-90WS AMC-110WS AMC-120WS AMC-150WS AMC-180WS AMC-200WS AMC-40WS-D AMC-50WS-D AMC-60WS-D AMC-70WS-D AMC-80WS-D AMC-90WS-D AMC-110WS-D AMC-120WS-D AMC-150WS-D AMC-180WS-D AMC-200WS-D
Name
|
Screw Compressor Type Water Chiller Machine
| |||||||
Model
|
AMC-40WS
|
AMC-50WS
|
RCMC-60W
|
AMC-70WS
|
AMC-80WS
|
AMC-90WS
| ||
Power resource
|
-
|
3Ø-380V-50HZ
| ||||||
Chilling capacity
|
kcal/h
|
113500
|
141900
|
166000
|
191800
|
220200
|
272600
| |
kw
|
132
|
165
|
193
|
223
|
256
|
317
| ||
Consumption
|
kw
|
31
|
38
|
43
|
51
|
58
|
76
| |
Operation current
|
A
|
54
|
66
|
75
|
87
|
96
|
123
| |
Startup current
|
A
|
218D/411D D
|
269D/508D D
|
290D/485D D
|
350D/585D D
|
350D/585D D
|
520D//801D D
| |
Capacity control
|
%
|
100-75-50-25-0
| ||||||
Compressor
|
Type
|
-
|
Half-closed and double-screw type
| |||||
Quantity
|
-
|
1
| ||||||
Startup type
|
-
|
Divided winding starting
| ||||||
Oil heater
|
W
|
200
|
300
| |||||
Chilled oil
|
Type
|
-
|
B320SH
| |||||
Filling quantity
|
L
|
9
|
15
|
22
| ||||
Refrigerant
|
Type
|
-
|
R-22
| |||||
Filling quantity
|
KG
|
21
|
26
|
30
|
35
|
40
|
50
| |
Throttling
|
-
|
Thermostatic expansion valve
| ||||||
Evaporator
|
Type
|
-
|
Tube-in-shell high efficient heat exchanger
| |||||
Chiller water flow
|
m³/h
|
23
|
28
|
33
|
38
|
44
|
55
| |
Pressure expense
|
KPa
|
54
|
54
|
54
|
57
|
57
|
57
| |
Water pipe joint
|
PT
|
3"
|
3"
|
3"
|
4"
|
4"
|
4"
| |
Condenser
|
Type
|
-
|
Tube-in-shell high efficient heat exchanger
| |||||
Chilling water flow
|
m³/h
|
30
|
37
|
43
|
50
|
57
|
71
| |
Pressure expense
|
KPa
|
54
|
54
|
57
|
57
|
59
|
59
| |
Water pipe joint
|
PT
|
2-1/2"
|
3"
|
3"
|
3"
|
3"
|
4"
| |
Protection device
|
-
|
High pressure switch, low pressure switch, Anti-freezing switch, fusible plug, compressor over-heat protection, motor over-heat protection, exhaust air over-heat protection, pump over-load protection, oil over-heat protection, phase reverse protection, voltage insecure, cooling water over-heat protection, chilled water flow protection, cooling water flow shortage protection, cooling tower over current protection, and so on.
| ||||||
External dimensions
|
L
|
mm
|
2175
|
2195
|
2245
|
2860
|
2860
|
2975
|
W
|
mm
|
935
|
935
|
935
|
1015
|
1015
|
1015
| |
H
|
mm
|
1430
|
1500
|
1655
|
1710
|
1710
|
1965
| |
A
|
mm
|
1100
|
1100
|
1100
|
1200
|
1200
|
1300
| |
B
|
mm
|
690
|
690
|
690
|
790
|
790
|
790
| |
C
|
mm
|
690
|
760
|
820
|
860
|
860
|
1000
| |
D
|
mm
|
170
|
190
|
240
|
240
|
240
|
270
| |
E
|
mm
|
100
|
100
|
120
|
120
|
120
|
160
| |
F
|
mm
|
75
|
80
|
80
|
125
|
105
|
100
| |
G
|
mm
|
240
|
240
|
230
|
475
|
475
|
400
| |
I
|
mm
|
75
|
156
|
170
|
200
|
200
|
315
| |
Net weight
|
Kg
|
1020
|
1060
|
1270
|
1370
|
1400
|
1870
| |
Operating weight
|
Kg
|
1120
|
1180
|
1420
|
1550
|
1580
|
2100
| |
Noise
|
dB(A)
|
74
|
76
|
78
|
Name
|
Screw Type Water Cooled Chilling Machine
| ||||||
Model
|
AMC-110WS
|
AMC-120WS
|
AMC-150WS
|
AMC-180WS
|
AMC-200WS
| ||
Power resource
|
-
|
3Ø-380V-50HZ
| |||||
Chilling capacity
|
kcal/h
|
312200
|
360300
|
470400
|
541800
|
621800
| |
kw
|
363
|
419
|
547
|
630
|
723
| ||
Consumption
|
kw
|
80
|
90
|
121
|
136
|
156
| |
Operation current
|
A
|
136
|
151
|
199
|
221
|
246
| |
Startup current
|
A
|
612D/943D D
|
665D/1023D D
|
465Y/1442D
|
586Y/1853D
|
650Y/2029D
| |
Capacity control
|
%
|
100-75-50-25-0
| |||||
Compressor
|
Type
|
-
|
Half-closed and double-screw type
| ||||
Quantity
|
-
|
1
| |||||
Startup type
|
-
|
Divided winding starting
|
Y-Δ
| ||||
Oil heater
|
W
|
300
| |||||
Chilled oil
|
Type
|
-
|
B320SH
| ||||
Filling quantity
|
L
|
22
|
28
| ||||
Refrigerant
|
Type
|
-
|
R-22
| ||||
Filling quantity
|
KG
|
57
|
66
|
86
|
99
|
113
| |
Throttling
|
-
|
Thermostatic expansion valve
| |||||
Evaporator
|
Type
|
-
|
Tube-in-shell high efficient heat exchanger
| ||||
Chiller water flow
|
m³/h
|
62
|
72
|
94
|
109
|
125
| |
Pressure expense
|
KPa
|
59
|
59
|
62
|
62
|
67
| |
Waterpipe joint
|
PT
|
4"
|
4"
|
5"
|
6"
|
6"
| |
Condenser
|
Type
|
-
|
Tube-in-shell high efficient heat exchanger
| ||||
Chilling water flow
|
m³/h
|
81
|
94
|
122
|
141
|
162
| |
Pressure expense
|
KPa
|
62
|
62
|
65
|
67
|
67
| |
Water pipe joint
|
PT
|
4"
|
4"
|
5"
|
5"
|
5"
| |
Protection device
|
-
|
High pressure switch, low pressure switch, Anti-freezing switch, fusible plug, compressor over-heat protection, motor over-heat protection, exhaust air over-heat protection, pump over-load protection, oil over-heat protection, phase reverse protection, voltage insecure, cooling water over-heat protection, chilled water flow protection, cooling water flow shortage protection, cooling tower over current protection, and so on.
| |||||
External dimensions
|
L
|
mm
|
2985
|
3010
|
3510
|
3590
|
3595
|
W
|
mm
|
1025
|
1055
|
1105
|
1150
|
1175
| |
H
|
mm
|
1975
|
1990
|
2140
|
2155
|
2195
| |
A
|
mm
|
1300
|
1300
|
1600
|
1600
|
1600
| |
B
|
mm
|
790
|
790
|
9000
|
900
|
980
| |
C
|
mm
|
1010
|
1010
|
1120
|
1120
|
1160
| |
D
|
mm
|
270
|
245
|
275
|
240
|
240
| |
E
|
mm
|
160
|
175
|
175
|
240
|
240
| |
F
|
mm
|
100
|
100
|
125
|
130
|
175
| |
G
|
mm
|
405
|
405
|
550
|
540
|
540
| |
I
|
mm
|
310
|
245
|
250
|
340
|
340
| |
Net weight
|
Kg
|
1870
|
2070
|
2790
|
2910
|
3240
| |
Operating weight
|
Kg
|
2220
|
2340
|
3120
|
3240
|
3760
| |
Noise
|
dB(A)
|
80
|
82
|
Remark:
1) Condition for parameter test: temperature of chilled water: inlet 12°C,outlet 7°C;temperature of chilling water: Inlet 30°C, outlet 35°C.
2) Noise test: 1m away from the due front of the machine, 1.5m high away from the machine(noise: below 30dB)
3) Any special requirements, have to be advised before order.
Please excuse for not note if some specifications of products are changed.
Double compressor specifications:
Name
|
Industrial Water Cooling Unit
| |||||||
Model
|
AMC-40WS-D
|
AMC-50WS-D
|
AMC-60WS-D
|
AMC-70WS-D
|
AMC-80WS-D
|
AMC-90WS-D
| ||
Power resource
|
-
|
3Ø-380V-50HZ
| ||||||
Chilling capacity
|
kcal/h
|
226200
|
283800
|
331100
|
383600
|
440300
|
547800
| |
kw
|
263
|
330
|
385
|
446
|
512
|
637
| ||
Consumption
|
kw
|
62
|
76
|
87
|
102
|
115
|
136
| |
Operation current
|
A
|
108
|
132
|
149
|
175
|
190
|
232
| |
Startup current
|
A
|
218D/411D D
|
269D/508D D
|
290D/485D D
|
350D/585D D
|
423D/686D D
|
520D//801D D
| |
Capacity control
|
%
|
100-75-50-25-0
| ||||||
Compressor
|
Type
|
-
|
Half-closed and double-screw type
| |||||
Quantity
|
-
|
2
| ||||||
Startup type
|
-
|
Divided winding starting
| ||||||
Oil heater
|
W
|
200x2
|
300x2
| |||||
Chilled oil
|
Type
|
-
|
B320SH
| |||||
Filling quantity
|
L
|
9x2
|
15x2
|
22x2
| ||||
Refrigerant
|
Type
|
-
|
R-22
| |||||
Filling quantity
|
KG
|
21x2
|
26x2
|
30x2
|
35x2
|
39x2
|
46x2
| |
Throttling
|
-
|
Thermostatic expansion valve
| ||||||
Evaporator
|
Type
|
-
|
Tube-in-shell high efficient heat exchanger
| |||||
Chiller water flow
|
m³/h
|
45
|
57
|
66
|
77
|
88
|
110
| |
Pressure expense
|
KPa
|
57
|
57
|
59
|
62
|
62
|
62
| |
Water pipe joint
|
PT
|
4"
|
4"
|
4"
|
5"
|
5"
|
5"
| |
Condenser
|
Type
|
-
|
Tube-in-shell high efficient heat exchanger
| |||||
Chilling water flow
|
m³/h
|
59
|
74
|
86
|
100
|
115
|
142
| |
Pressure expense
|
KPa
|
51
|
54
|
59
|
59
|
59
|
62
| |
Water pipe joint
|
PT
|
2-1/2"x2
|
3"
|
3"x2
|
3"x2
|
3"x2
|
4"x2
| |
Protection device
|
-
|
High pressure switch, low pressure switch, Anti-freezing switch, fusible plug, compressor over-heat protection, motor over-heat protection, exhaust air over-heat protection, pump over-load protection, oil over-heat protection, phase reverse protection, voltage insecure, cooling water over-heat protection, chilled water flow protection, cooling water flow shortage protection, cooling tower over current protection, and so on.
| ||||||
External dimensions
|
L
|
mm
|
2850
|
2850
|
3040
|
3130
|
3140
|
3760
|
W
|
mm
|
1150
|
1150
|
1250
|
1250
|
1250
|
1400
| |
H
|
mm
|
1450
|
1450
|
1760
|
1790
|
1810
|
2030
| |
A
|
mm
|
1300
|
1300
|
1300
|
1600
|
1600
|
1600
| |
B
|
mm
|
1040
|
1040
|
1140
|
1140
|
1140
|
1290
| |
C
|
mm
|
770
|
770
|
955
|
970
|
975
|
1085
| |
D
|
mm
|
215
|
215
|
275
|
270
|
270
|
265
| |
E
|
mm
|
100
|
100
|
120
|
120
|
120
|
175
| |
F
|
mm
|
230
|
230
|
275
|
300
|
275
|
375
| |
G
|
mm
|
410
|
410
|
400
|
245
|
400
|
545
| |
I
|
mm
|
70
|
70
|
245
|
250
|
245
|
250
| |
Net weight
|
Kg
|
1790
|
1790
|
2340
|
2420
|
2500
|
3580
| |
Operating weight
|
Kg
|
1920
|
1970
|
2520
|
2620
|
2710
|
3920
| |
Noise
|
dB(A)
|
72
|
76
|
80
|
Name
|
High Capacity Industrial Water Chiller
| ||||||
Model
|
AMC-110WS-D
|
AMC-120WS-D
|
AMC-150WS-D
|
AMC-180WS-D
|
AMC-200WS-D
| ||
Power resource
|
-
|
3Ø-380V-50HZ
| |||||
Chilling capacity
|
kcal/h
|
623500
|
721500
|
940000
|
1083600
|
1243600
| |
kw
|
725
|
839
|
1093
|
1260
|
1446
| ||
Consumption
|
kw
|
160
|
180
|
230
|
272
|
305
| |
Operation current
|
A
|
273
|
305
|
373
|
452
|
503
| |
Startup current
|
A
|
612D/943D D
|
665D/1023D D
|
465Y/1442D
|
586Y/1853D
|
650Y/2029D
| |
Capacity control
|
%
|
100-75-50-25-0
| |||||
Compressor
|
Type
|
-
|
Half-closed and double-screw type
| ||||
Quantity
|
-
|
2
| |||||
Startup type
|
-
|
Divided winding starting
|
Y-Δ
| ||||
Oil heater
|
W
|
300x2
| |||||
Chilled oil
|
Type
|
-
|
B320SH
| ||||
Filling quantity
|
L
|
22x2
|
28x2
| ||||
Refrigerant
|
Type
|
-
|
R-22
| ||||
Filling quantity
|
KG
|
54x2
|
61x2
|
78x2
|
92x2
|
104x2
| |
Throttling
|
-
|
Thermostatic expansion valve
| |||||
Evaporator
|
Type
|
-
|
Tube-in-shell high efficient heat exchanger
| ||||
Chiller water flow
|
m³/h
|
125
|
144
|
188
|
217
|
249
| |
Pressure expense
|
KPa
|
65
|
65
|
67
|
67
|
69
| |
Water pipe joint
|
PT
|
6"
|
6"
|
6"
|
8"
|
8"
| |
Condenser
|
Type
|
-
|
Tube-in-shell high efficient heat exchanger
| ||||
Chilling water flow
|
m³/h
|
162
|
188
|
244
|
282
|
323
| |
Pressure expense
|
KPa
|
62
|
62
|
65
|
67
|
67
| |
Water pipe joint
|
PT
|
4"x2
|
4"x2
|
5"x2
|
5"x2
|
5"x2
| |
Protection device
|
-
|
High pressure switch, low pressure switch, Anti-freezing switch, fusible plug, compressor over-heat protection, motor over-heat protection, exhaust air over-heat protection, pump over-load protection, oil over-heat protection, phase reverse protection, voltage insecure, cooling water over-heat protection, chilled water flow protection, cooling water flow shortage protection, cooling tower over current protection, and so on.
| |||||
External dimensions
|
L
|
mm
|
3760
|
3760
|
4100
|
4100
|
4250
|
W
|
mm
|
1400
|
1400
|
1600
|
1750
|
1750
| |
H
|
mm
|
2040
|
2080
|
2260
|
2290
|
2360
| |
A
|
mm
|
1600
|
1600
|
1600
|
1600
|
1600
| |
B
|
mm
|
1290
|
1290
|
1480
|
1630
|
1630
| |
C
|
mm
|
1130
|
1135
|
1240
|
1270
|
1305
| |
D
|
mm
|
265
|
265
|
290
|
290
|
290
| |
E
|
mm
|
175
|
175
|
240
|
240
|
250
| |
F
|
mm
|
375
|
375
|
450
|
450
|
430
| |
G
|
mm
|
545
|
545
|
500
|
500
|
775
| |
I
|
mm
|
250
|
250
|
100
|
100
|
90
| |
Net weight
|
Kg
|
3750
|
3880
|
5050
|
5340
|
5600
| |
Operating weight
|
Kg
|
4110
|
4250
|
5490
|
5830
|
6260
| |
Noise
|
dB(A)
|
80
|
82
|
Our company is a famous supplier of Water Cooling Tower, Air-cooled Water Chiller, Water-cooled Water Chiller, Industrial Water Chiller, Mold Temperature Controller, Screw-compressor Water Chiller etc. Welcome to contact us to know more
Remark:
1) Condition for parameter test: temperature of chilled water: inlet 12°C,outlet 7°C;temperature of chilling water: Inlet 30°C, outlet 35°C.
2) Noise test: 1m away from the due front of the machine, 1.5m high away from the machine (noise: below 30dB)
3) "-D" means double compressor.
4) Any special requirements have to be advised before order.
Please excuse for not note if some specifications of products are changed.